• 1.3 Qisqa tutashuv toklarini hisoblash natijalari .
  • 2.Transformatorning rele himoyasi.
  • 2.2 Transformatorning o’ta yuklanishdan himoyalash
  • K3 nuqtadagi qisqa tutashuv toklari




    Download 0.84 Mb.
    bet5/12
    Sana24.11.2022
    Hajmi0.84 Mb.
    #31695
    1   2   3   4   5   6   7   8   9   ...   12
    Bog'liq
    Oilova Maftuna Rele tayyor (2)
    Алиев Эльдар Муратович, 12 bilet, 1-amaliy mashg\'ulot, 3.1.Alijonova Sarvinoz Rovshan qizi, Go’daklik davrida psixik rivojlanishda kattalar bilan emotsional muloqotning axamiyati, hjftgyh, 3-ITI xisobot C.Mansurov, Microsoft Access dasturi bilan ishlash, MS WINDOWS 7 8 10 OPERATSION TIZIMLARI VA ULARDAGI YANGI IMKONIYATLAR, To\'m 5- variant 25 talik , Fashizm - Vikipediya, 5-синф, azizullo ppt, 8
    K3 nuqtadagi qisqa tutashuv toklari.
    Xk3=XIEM+XL2=0,83+0,39=1,22
    Ik3c=EIEM*Ibk3/Xk3=
    Ik3cd=Ecd*Ibk3/Xcd=
    Ik3max=Ik3c+4*Ik3cd=27,07+4*0,26=28,11
    Ik3min=0,87*Ik3c=0,87*27,07=23,55
    K4 nuqtadagi qisqa tutashuv toklari .
    Zk4= =162,82
    Ik4c=Ec*Ibk4/Zk4=
    Ik4max=Ik4c=4,44
    Ik4min=0,87* Ik4c=0,87*4,44=3,86

    1.3 Qisqa tutashuv toklarini hisoblash natijalari.


    1.1-jadval

    Qisqa tutashuv nuqtasi

    K1

    K2

    K3

    K4

    IEM dan Ikc, kA

    40

    13,42

    27,07

    4,44

    Elektr dvigatellardan Ikd, kA




    0,21

    0,26




    Maksimal tok Ikmax, kA

    40

    13,84

    28,11

    4,44

    Minimal tok Ikmin, kA

    34,8

    11,67

    23,55

    3,86


    2.Transformatorning rele himoyasi.


    Boshlang’ich ma’lumot.
    Transformatorning quvvati ST=SBPP=1600 kVA
    Yuqori kuchlanishi UTyuqori=10,5 kV
    Past kuchlanishi UTpast=0,4 kV
    Past kuchlanish tomonidagi maksimal va minimal qisqa tutashuv toklarini 1.1-jadvaldan olamiz;
    Ik2max=13,84 kA
    Ik2min=11,67 kA
    Transformatorni qisqa tutashuvlardan himoya qilish uchun sabr vaqtiga ega bo’lmagan tez ishlovchi quyidagi himoyalar qo’llaniladi tok otsechkasi, differensial himoya va gaz himoyasi.
    Transformatorning past kuchlanish (PK) tomonida qisqa tutashuv bo’lganda yuqori kuchlanish (YK) tomondagi tok.
    I1k2max=Ik2max*(Upk/Uyk)=13,84*
    I2k2min=Ik2min*(Upk/Uyk)=11,67*
    2.1. Transformatorning ichki qisqa tutashuvdan bo’ylanma differensial himoya orqali himoyalash hisobi.

    2.1.1-rasm.Transformatorning bo’ylama differensial himoyasi ishlash prinspi.
    Bo’ylanma differensial himoya quyidagi tartibda hisoblanadi
    Transformatorning nominal toklarini aniqlaymiz;
    Yuqori kuchlanish tomonida
    Inom1=ST/1,73*UTyuq=
    Past kuchlanish tomonida
    Inom2=ST/1,73*UTpast=
    Tok transformatorining hisobiy transformatsiya koeffitsientlarini hisoblaymiz;
    Yuqori kuchlanish tomonida
    K11x=2*1,73*Inom1/5= Past kuchlanish tomonida
    K12x=2*Inom2/5=
    Spravochnikdan transformatsiya koeffitsientining standart qiymatlarini tanlaymiz
    K11=750
    K12=10000
    Ikkilamchi toklar
    I12=1,73*Inom1/K11= A
    I22=Inom2/K12= A
    Asosiy tomon sifatida past kuchlanish tomonni tanlaymiz.
    Differensial himoyaning ishga tushish toki quyidagi shartlarga asosan tanlanadi.

    1. Kuch transformatori magnitlovchi tokning sakrashidan chetlashtirish

    Ixi=Kz*InomT=1,3*2312.138=3005.7794A
    Bu еrda Kz=1,3 (PHT-565 rele uchun), Inom.TR=Inom2

    1. Nobalans toklarni chetlashtirish

    I’nb=Kap*Kb*f1*Ikmax=1*1*0,1*13,84*1000=13,84A
    bu еrda Kap=1, Kb=1, f1=0,1.
    I”nb=+/- DN*I1k2max/100=
    Bu еrda +/- DN=9 kuchlanishni rostlashni to’la rostlash chegarasining qiymati.
    Inbmax=I’nb+I”nb=1384+1,2456=1385,25A
    Differensial himoyaning ishga tushish toki
    Ixi=1,3*Inbmax=1,3*1385,25=1800,82 A
    Sezgirlik koeffitsienti
    Kc=Ik2min/Ixi=
    Bu еrda Ik2min=11.67 kA=11670 A. himoya еtarli sezgirlikka ega.
    Relening ishga tushish toki
    Iri=Ixi/K12=
    PHT relesiga qo’yilishi zarur bo’lgan hisobiy o’ramlar sonini aniqlaymiz
    Was.xis=Fc/Iri=
    Bu еrda Fc=100 o’ram A, Was=99 ni qabul qilamiz.
    Asosiy bo’lmagan tomon uchun hisobiy o’ramlar soni
    Was.bo’l.xis=Was* 99* =41666
    Was.bo’l.xis=41666qabul qilamiz
    Nobalans toki
    I’’’nb=[(Was.xis-Was)*Imax/Wasxis= =0,49kA=490,5A
    Umumiy nobalans toki
    Inb=I’nb+I’’nb+I’’’nb=1384+1,24+0,49=1385,73 A
    Himoyaning ishga tushirish toki
    Ixi=Kz*Inbmax=1,3*1385,73=1801,449 A
    Himoyaning sezgirligi
    Kc=5,8

    2.2 Transformatorning o’ta yuklanishdan himoyalash



    2.2.1-rasm. Transformatorning o’ta yuklanishdan himoyasi.
    O’ta yuklanishdan himoyaning ishga tushish toki quyidagi ifodaga asosan hisoblanadi
    Ixi=Kz*Inom/Km
    Bu еrda Kz=1,05 zaxira koeffitsienti, KM=0,8 tok relesining qaytish koeffitsienti
    Relening ishga tushish toki
    Iri=Kcx*Ixi/K1
    Bu еrda Kcx=sxema koeffitsienti, K1-tok transformatorining transformatsiya koeffitsienti.
    Ximoyaning sabr vaqti
    t=tx+ t
    bu еrda tx-MTX ning sabr vaqti ; t=5c ; Ir va t ga asosan tok va vaqt relesi tanlanadi.
    Transformatorning nominal toki
    Inom1=ST/1,73*UTyuq=
    Odatda, transformatorning o’ta yuklanishi simmetrik bo’lishi sababli ximoyani bir fazali maksimal tok himoyasi (MTX) ko’rinishida bajaramiz
    Ixi=Kz*Inom/Km=1,05*
    Relening ishga tushish toki
    Iri=Kcx*Ixi/K1=
    O’ta yuklanishdan himoyaning ishlash vaqti tashqi qisqa tutashuvlardan himoyaning ishlash vaqtidan bir pog’ona yuqori qilib olinadi.
    t=tMTX+ t=1,5+0,5=2c.
    Irixi/K11
    3,25<
    PT-10/10 turdagi tok ЭВ-132 turdagi vaqt relesini tanlaymiz.