TOP Server Release Notes (5.17.495.0) February 24, 2015
|
bet | 4/20 | Sana | 25.09.2020 | Hajmi | 176,31 Kb. | | #11681 |
TOP Server Release Notes (5.17.495.0) February 24, 2015
Added Scheduler Plug-In to the Plug-Ins feature tree.
Server Admin
Fixed an issue where selecting the Security Policies tab in the Administration Utility would cause an “Unable to load project C:\ProgramData\Software Toolbox\TOP server\V5\default.opf” error message with some drivers.
Server Configuration
Corrected a failure to show the proper string/message in the status bar in some situations.
Added support for 64-bit data types, including QWord, LLong, and arrays of these two types. These data types are now available in the Tag Properties drop-down menu and Multiple Tag Generation utility, but cannot be used in scaling.
Removed the ability for Boolean or Boolean Arrays and Strings or String Arrays to be used as scaling types.
Adjusted the data type lists in the Tag Properties, Multiple Tag Generation, and Quick Client Add Item dialogs to display in the same order for consistency.
Server Runtime
Enhanced the driver library to support prioritization of explicit reads. This is only used by the new Scheduler Plug-In; read behavior for existing clients is not affected.
Added support for 64-bit data types, including QWord, LLong, and arrays of these two types. These data types are supported by select interfaces and drivers.
Application Report Utility
Enhanced the report utility to only capture Kepware-specific process dumps. Prior to this change, the utility gathered process dumps from other applications, which made the report files larger than needed.
Corrected a failure to detect and run reports on installed TOP Server V5 when TOP Server V4 or OEM versions were also installed on the system.
OPC Quick Client
Adjusted the order of the data types listed in the Add Item dialog to be consistent with other products.
Added support for 64-bit data types, including QWord, LLong, and arrays of these two types.
Client Interfaces
OPC DA Server
Added support for 64-bit data types, including QWord, LLong, and arrays of these two types.
Fixed an issue where coercing arrays into other data types could result in memory leaks or access to invalid memory.
OPC UA Server
Added support for 64-bit data types, including QWord, LLong, and arrays of these two types.
Removed a delay in server startup caused by the server attempting to resolve invalid endpoint adapter names.
OPC HDA Server
Enhanced aggregate support to include Interpolative, Time Average, Total, Minimum Actual Time, and Maximum Actual Time.
Enhanced ReadProcessed transactions to handle reverse reads and support multiple aggregate types.
Added support for synchronous ReadAtTime.
Fixed multiple issues with ReadProcessed calls returning the correct quality and sub-quality when the request intervals were outside the bounds of valid data in the Local Historian.
Enhanced the handling of ReadProcessed calls with many small intervals to be more efficient and to timeout gracefully when the request size is unreasonable.
Updated ReadProcessed transactions to handle invalid aggregates with the item error set to OPC_E_NOT_AVAIL and return code S_FALSE.
Added support for canceling outstanding ReadProcessed and ReadAtTime transactions when the server is shutdown or reinitialized.
ReadProcessed now attempts conversion of string data it receives as part of its search for valid bounding data.
Renamed the "Time Average" aggregate (returned from a GetAggregates call) to "TimeAverage" to improve compatibility with MATLAB.
Plug-Ins
Advanced Tags
Removed repeated error messages when the plug-in fails to add a tag reference.
Fixed a memory leak that was caused by the plug-in failing to load a ‘Complete’ tag reference.
EFM Exporter
Added support for FLOWCAL Transaction Queue. The EFM Exporter can now push gas data directly to FLOWCAL’s Oracle database.
Removed the password field from CSV import/export for the Database Exporter. CSV files exported from previous versions still import correctly, but the password is ignored. Existing exporters that are updated by CSV import retain the original password and new exporters created by the import have a blank password.
Replaced the "Toggle On/Off" traffic light button with "Enable" and "Disable" buttons.
Fixed an issue where the context menu could appear in the wrong location if the configuration window was condensed.
Fixed an issue where modifying the CSV Exporter mappings and deleting the CSV file could result in improper output.
Local Historian
Added the ability to delete the datastore.
Added support for the CSV import and export of historical tags under a historical tag group.
Added support for 64-bit data types, including QWord and LLong.
Added buttons to browse the directories for the Datastore Location and Import Location.
Enhanced the multi-tag edit dialog to allow users to only edit a subset of the tag properties. Leaving a field blank will not apply any changes for that field to the selected tags.
Added the new “Historian Service Status” field to the Status view to help troubleshoot issues when the Historian service is not running. The field shows started, stopped, disabled, or not installed.
Simplified the tag dialog to allow dynamic or static tag address creation.
Fixed a defect where tags would not be renamed if the server channel, device, or tag was renamed. This could occur in cases where the name changed in case only.
Fixed an issue where closing the configuration when the Tag Browser was being used could result in the configuration crashing.
Tag groups are now given a default name upon creation.
Fixed an issue where the Value Display view was not updated with new settings until a new value was recorded for the tag. The view is now updated when the setting changes are made.
Fixed an issue that occurred when adding String or Boolean tags where the deadband option was not shown as disabled. These data types do not support deadband.
Fixed a missing help file link from the tag dialog page.
Media Level Redundancy
Added support for 64-bit data types, including QWord, LLong, and arrays of these two types. These types can be used in redundant items and as the monitor item.
Security Policies
Resolved an issue where certain device properties could not be edited if the Security Policies Plug-In applied a custom access rule on the device. The Security Policies Plug-In created a reference on the device that the device interpreted as a client reference. By default, TOP Server does not allow device edits if a client is referencing the device. The Security Policies Plug-In is no longer treated as a client reference and allows edits.
Scheduler (NEW)
Added the new Scheduler Plug-In, which decouples the client scan rate from the rate at which devices are polled. The server can poll for data once a day, every five minutes, and so forth. Clients get updates from the server cache.
Drivers
ABB Totalflow
Increased the maximum channel limit from 512 to 1024.
Allen-Bradley Ethernet
Added support for SoftPLC address ranges. SoftPLC does not support the ASCII memory type.
Fixed an issue where the PLC5 model could read the wrong memory location for string types beyond element 780.
Allen-Bradley ControlLogix Ethernet
Added support for V23 and V24 firmware.
Updated the driver to work with future-generation devices and firmware. Before this fix, the driver experienced a communications failure with these devices.
Increased the maximum channel limit from 256 to 1024.
Fixed an issue where automatic tag generation from an L5K file failed if the L5K contained an AOI parameter that aliased another parameter. AOI alias parameters are not supported in automatic tag generation and should not be automatically generated.
For Logix FRN V24, updated Predefined Data Types for offline automatic tag generation and added new members to AXIS_CIP_DRIVE, AXIS_CONSUMED, AXIS_GENERIC, AXIS_GENERIC_DRIVE, AXIS_SERVO, AXIS_SERVO_DRIVE, AXIS_VIRTUAL, and MOTION_GROUP per Logix FRN V24 changes.
Allen-Bradley DF1
Fixed an issue where the driver produced a syntax error during tag validation if the data type was not supported. Some clients add items with a set data type regardless of the address. The driver now responds with bad type, allowing the driver library to validate again with the default type.
AutomationDirect DirectNet
Corrected an issue where the driver would produce a syntax error during tag validation if the data type was not supported. Some clients add items with a set data type regardless of the address. The driver now responds with bad type, allowing the driver library to validate again with the default type.
Fixed an issue where Data Words Timers (V0-V377) and Counters (V1000-V1177) default to the BCD data type even if the address was a bit within data type; Bit within BCD is not supported. For V addresses with bit-access syntax, the driver now defaults to Short data type for the bit range 0- to 15 and to Long data type for bit range 16 to 31.
BACnet
Fixed an issue where automatic tag generation failed if the device did not support segmentation. This issue was introduced in TOP Server version 5.15.
Enhanced the driver to support manual configuration of the BACnet MAC address. This allows the driver to communicate through a gateway to other BACnet network types.
Cutler-Hammer
Corrected an issue where the driver would produce a syntax error during tag validation if the data type was not supported. Some clients add items with a set data type regardless of the address. The driver now responds with bad type, allowing the driver library to validate again with the default type.
DNP3 Master Ethernet
Added support for 10 ms update rates to Event Class 1, 2, and 3 polling intervals.
Fixed an issue where malformed packets could disrupt communications.
Fixed an issue where an out-of-bound read vulnerability could exhaust resources and prevent the driver from working.
DNP3 Master Serial
Added support for 10 ms update rates to Event Class 1, 2, and 3 polling intervals.
Fixed an issue where malformed packets could disrupt communications.
Fixed an issue where an out-of-bound read vulnerability could exhaust resources and prevent the driver from working.
Fisher ROC Serial
Spaces are no longer allowed in liquid and gas meter names
Fisher ROC+ Serial
Spaces are no longer allowed in liquid and gas meter names.
GE Ethernet
Fixed an issue where the driver posted the error message "Device
returned error code 0xFDFF reading symbolic variable data" when certain devices respond with unexpected bytes. The driver was updated to handle these responses.
IEC 60870-5-104
Fixed an issue where timestamp values sent from the device with the day-of-week field set to 0 (unused) were not displayed correctly in the Quick Client. The driver now calculates the correct day-of-week based on the timestamp.
IEC 61850 MMS Client
Fixed an issue where tags were not being generated correctly from SCL files when the type name is appended to the data attribute name in the SCL file (for example, "mag.f").
MTConnect
Added schema files to support Version 1.2 and 1.3 of the MTConnect standard.
OMRON FINS Serial
Corrected an issue where the driver would produce a syntax error during tag validation if the data type was not supported. Some clients add items with a set data type regardless of the address. The driver now responds with bad type, allowing the driver library to validate again with the default type.
OMRON FINS Ethernet
Corrected an issue where the driver would produce a syntax error during tag validation if the data type was not supported. Some clients add items with a set data type regardless of the address. The driver now responds with bad type, allowing the driver library to validate again with the default type.
OPC DA Client
Added support for 64-bit data types, including QWord, LLong, and arrays of these two types.
OPC UA Client
Enhanced the driver to reconnect the UA session after encountering an invalid Session ID error.
The Device _Error flag is now set if the driver is unable to connect on the initial connection.
Added support for 64-bit data types, including QWord, LLong, and arrays of these two types.
OPC XML DA
Added support for 64-bit data types, including QWord, LLong, and arrays of these two types.
Siemens TCP/IP Ethernet
Fixed an issue where tags of type ‘Date’ could result in other tag values not being updated. This only occurred with tags that were in the same block as the Date tag.
Added support for HEXSTRING data types.
Siemens TCP/IP Slave Ethernet
Fixed a runtime crash that could occur if there was a socket error while reading unsolicited data.
Simulator
Added support for 64-bit data types, including QWord, LLong, and arrays of these two types to both the 8-bit and 16-bit device models.
UCON
Fixed an issue where global function blocks with commands CCmdWriteDeviceID or CCmdTestDeviceID could cause an XML configuration to fail to load.
|
| |