Namangan Institute of Engineering and Technology Pdf ko'rish
|
bet | 54/693 | Sana | 13.05.2024 | Hajmi | 15,56 Mb. | | #228860 |
Bog'liq ТўпламNamangan Institute of Engineering and Technology
nammti.uz
10.25.2023
Pg.46
1- rasm Kuchlanishning simmetrik va nosimmetrik holatlarining vektor diogrammada
ko‘rinishi
Kuchlanish nosimmetriyasi quyidagi ko‘rsatkichlar bilan xarakterlanadi:
Nominal liniya kuchlanishiga
𝑈
𝑛𝑜𝑚
asosiy chastotaning teskari ketma-ketlikdagi
kuchlanishining
𝑈
2
nisbati bilan teng bo‘lgan kuchlanish nosimmetriyasini teskari ketma-ketlik
koeffitsienti
𝐾
2𝑈
,
%;
Nominal faza kuchlanishiga
𝑈
𝑛𝑜𝑚
asosiy chastotaning nol ketma-ketlikdagi kuchlanishining
𝑈
0
nisbati bilan teng bo‘lgan kuchlanish nosimmetriyasini nol ketma-ketlik koeffitsienti
𝐾
0𝑈
,
%;
GOST bo‘yicha elektr tarmog‘iga umumiy ulanish nuqtalarida kuchlanish nosimmetriyasini
teskari ketma-ketlik koeffitsientining normal va ruxsat etilgan chegaraviy qiymatlari mos ravishda
2,0 va 4,0% ni tashkil qiladi.
Nominal kuchlanishi 0,38 kV bo‘lgan to‘rt simli elektr tarmoqlariga umumiy ulanish
nuqtalarida kuchlanish nosimmetriyasini nol ketma-ketlik koeffitsientining normal ruxsat etilgan va
ruxsat etilgan chegaraviy qiymatlari mos ravishda 2,0 va 4,0% ni tashkil etadi.
Teskari ketma-ketlik bo‘yicha nosimmetriya koeffitsiyenti:
𝐾
2𝑈
=
𝑈
2
𝑈
𝑛𝑜𝑚
∙ 100%
(1)
bu yerda,
𝑈
2
- uchlanishning teskari ketma-ketligining amaldagi qiymati.
𝑈
2
= 𝐼
2𝑒𝑘𝑣
∙ 𝑍
2Σ
(2)
bu yerda,
𝐼
2𝑒𝑘𝑣
– yuklama nosimmetriyasidan yuzaga keladigan teskari ketma-ketlikning
ekvivalent tok.
𝑍
2Σ
– tarmoq teskari ketma-ketlik qarshiliklari yig‘indisi.
Kuchlanishlar nosimmetriyasining kelib chiqishi natijasida tarmoqda qo‘shimcha quvvat
yo‘qolishiga, bir fazali iste’molchilarning ishlash muddatini kamayishiga olib keladi.
Shuning uchun nosimmetrik holatlarni boshqarish, kuchlanish va toklar nosimmetriyasini
kamaytirish usullari va texnik vositalaridan foydalanish yuqoridagi muammolarni kamaytirishga